Description

Differential air pressure switch for filters, fans, air ducts and air conditioning and ventilation systems.

Use

Differential air pressure switch for the control and security in air conditioning systems for the signalling of :
- stop of the fans
- clogging of filters
- power interruption of electric batteries in the absence of air.
Installed in environments with air and non-aggressive and non-flammable gases.

Operating data

Pa : pressure drop in Pascal

ModelsEPDS-200EPDS-300EPDS-500EPDS-600EPDS-1500EPDS-4500
Scala
Pa
20-20030-30030-50040-600100-1500500-4500
Accuratezza±8 Pa al limite inferiore, ±15 % al limite superiore±20 Pa al limite inferiore, ±15 % al limite superiore±100 Pa al limite inferiore, ±15 % al limite superiore
Differenziale commutazione (Pa)2025253580250
Attacchi pressioneØ5 mm
Contatti elettriciNO/NC, contatto in scambio
Caratteristiche elettriche250 Vac, 0,1 A (res.)250 Vac, 3 A (res.), 2 A (ind.)
Cablaggio elettricoM16 - 1,5mm2
Temperatura di funzionamento (°C)-20...+60
Protection ratingIP54

Installation

Price list

Tubes and pressure sockets to be purchased separately.

ModelsEuro
EPDS-20049,83
EPDS-30049,83
EPDS-50049,83
EPDS-60049,83
EPDS-150049,83
EPDS-450049,83

Accessories

Descrizioneeuro
Kit tubetti e prese di pressione per pressostato differenziale EPDS9,28